Network Communications
10
10.3 BACnet Communications
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 703
Object ID
Object Name
(Network Display, if
Different)
Modbus Reg. Precision Range Units PV Access
AI8 Inverter Model o2-04 0508h XXXXX 0-65535 - R
AI9 Rated Current n9-01 05D0h
XXXX.X (for drives
rated higher than 11
kVA)
XXX.XX (for drives
rated 11 kVA or lower)
0-6553.5 (for drives
rated higher than 11
kVA)
0-65535 (for drives
rated 11 kVA or lower)
A R
AI10 Motor Current UB-01 8780h
XXXX.X (for drives
rated higher than 11
kVA)
XXX.XX (for drives
rated 11 kVA or lower)
0-6553.5 (for drives
rated higher than 11
kVA)
0-65535 (for drives
rated 11 kVA or lower)
A R
AI11 Contactor Voltage 8790h XXXXX 0-65535 V R
■ Analog Output Objects
Object ID
Object Name
(Network Display)
Modbus Reg. Precision Range Units PV Access
AO1
Drive Terminal FM
Analog Output Level
Command (set H4-01 =
0)
(Drv Anlg Out1 Level)
0007h XXX.X 0-100.0 % C
AO2
Drive Terminal AM
Analog Output Level
Command (Set H4-04 =
0)
(Drv Anlg Out2 Level)
0008h XXX.X 0-100.0 % C
■ Analog Value Objects
Object ID
Object Name
(Network Display, if
Different)
Modbus Reg. Precision Range Units PV Access
AV1
Drive Operation
Command
(Operation Cmd)
Note:
Do not command
bypass using AV1.
Use BV58 to BV71
instead.
0001h - 0-65535 Bitmap C
AV2 Frequency Cmd 0002h
XXX.XX
Determined by o1-03
0-600.00 Determined by o1-03 C
AV3 PI Setpoint Cmd 0006h XXX.XX 0-100.00 % C