Network Communications
10
10.3 BACnet Communications
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 705
Object ID
Object Name
(Network Display, if
Different)
Modbus Reg. Precision Range Units PV Access
AV7
Fault Details
bit 0: oC
[Overcurrent], GF
[Ground Fault]
bit 1: ov
[Overvoltage]
bit 2: oL2 [Drive
Overload]
bit 3: oH1 [Heatsink
Overheat], oH2
[External Overheat
(H1-XX=B)]
bit 4 to 6: Reserved
bit 7: EF to EF7
[External Fault]
bit 8: CPFxx
[Hardware Fault]
(includes oFAxx)
bit 9: oL1 [Motor
Overload], oL3
[Overtorque
Detection 1], UL3
[Undertorque
Detection 1]
bit A: Reserved
bit B: Uv [DC Bus
Undervoltage]
bit C: Uv1[DC Bus
Undervoltage], Uv2
[Control Power
Undervoltage], Uv3
[Soft Charge
Answerback Fault]
bit D: LF [Output
Phase Loss], PF
[Input Phase Loss]
bit E: CE [Modbus
Communication
Error], bUS [Option
Communication
Error]
bit F: oPr [Keypad
Connection Fault]
0021h - 0-65535 Bitmap R
AV8
Data Link Status
bit 0: Writing Data
bit 1: Reserved
bit 2: Reserved
bit 3: Upper or lower
limit error
bit 4: Data
conformity error
bit 5: Writing to
EEPROM
bit 6 to F: Reserved
0022h - 0-63 Bitmap R
AV9 Frequency Reference 0040h
XXX.XX
Determined by o1-03
0-600.00 Determined by o1-03 R
AV10 Output Frequency 0041h
XXX.XX
Determined by o1-03
0-600.00 Determined by o1-03 R
AV11 Output Voltage 0045h XXXX.X 0-6553.5 V R
AV12 Output Current 0026h XXXX.X 0-6553.5 A R
AV13 Output Power 0047h
XXXX.X > 11kVA
XXX.XX <= 11kVA
0-6553.5 > 11kVA
0-655.35 <= 11kVA
KW R
AV14 Torque Reference 0048h XXXX.X 0-100.0 % R
AV15
Drive Multi-Function
Input Status
(MF Input Status)
002Bh XXX 0-127 Bitmap R
AV16 Drive Status 2 002Ch XXXXX 0-65535 Bitmap R
AV17
Drive Multi-Function
Output Status
(MF Output Status)
002Dh XXX 0-135 Bitmap R