Setting 2: MEMOBUS/Modbus Communications
This setting requires entering the Run command via serial communications by connecting the RS-485/422 serial
communication cable to control terminals R+, R-, S+, and S- on the removable terminal block.
Setting 3: Option Card
This setting requires entering the Run command via the communication option board by plugging a communication option
board into the CN5-A port on the control PCB. Refer to the option board manual for instructions on integrating the drive into
the communication system.
Note: If b1-02 is set to 3, but an option board is not installed in CN5-A, an oPE05 operator programming error will be displayed on the digital
operator and the drive will not run.
n
b1-03: Stopping Method Selection
Selects how the drive stops the motor when the Run command is removed or when a Stop command is entered.
No. Parameter Name Setting Range Default
b1-03 Stopping Method Selection 0 to 3 0
Setting 0: Ramp to Stop
When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the
active deceleration time. The default deceleration time is set to parameter C1-02.
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection, Zero Speed Control,
or Short Circuit Braking. Refer to b2-01: DC Injection Braking Start Frequency on page 96 for details.
Setting 1: Coast to Stop
When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to
stop. The stopping time is determined by the inertia and the friction in the driven system.
Drive output is shut off
Run
command
Output
frequency
Motor speed
ON OFF
Figure 4.8 Coast to Stop
Note: After a stop is initiated, any subsequent Run command entered will be ignored until the minimum baseblock time (L2-03) has expired. Do
not enter Run command until it has come to a complete stop. Use DC Injection at Start (Refer to b2: DC Injection Braking and Short
Circuit Braking on page 185) or Speed Search (Refer to b3: Speed Search on page 186) to restart the motor before it has completely
stopped.
Setting 2: DC Injection Braking to Stop
When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time
(L2-03). When the minimum baseblock time has expired, the drive will inject the amount DC Injection Braking is set in
parameter b2-02 into the motor windings to brake the motor. The stopping time in DC Injection Braking to Stop is significantly
faster compared to Coast to Stop.
4.6 Basic Drive Setup Adjustments
94
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

Table of Contents

Other manuals for YASKAWA P1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA P1000 and is the answer not in the manual?

YASKAWA P1000 Specifications

General IconGeneral
Operating Temperature-10°C to +50°C (14°F to 122°F)
Cooling MethodFan Cooled
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
Frequency Range0.1-400 Hz
Power Rating0.4 kW to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit, Ground Fault
Protection FeaturesElectronic Thermal Overload Protection
CommunicationModbus RTU
Communication InterfaceRS-485
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Enclosure RatingIP20