JOHNSON CONTROLS
77
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
FORM 102.20-N1 
ISSUE DATE: 7/06/2016
3
WATER TREATMENT
Any copper tube coils may be attacked by acid con-
densate. Treat the coils with boiling water and CO
2 
 to 
remove the condensate, and to assure longer tube life.
Freeze Protection
Chilled water, hot water, and steam coils can be dam-
aged during freezing weather. Take the following pre-
cautionary measures to prevent freezing:
• Positive coil freeze protection must be used in 
installations where any part of the water coil is 
subjected to temperatures of 32°F or lower, which 
may be accomplished by using a suitable anti-
freeze solution. If the coil is not in use, it is rec-
ommended to drain the coil completely, and blow 
dry the inside of the tubes with compressed air.
• Afterdraining,ushthecoilswithananti-freeze
solution such as 50% glycol and 50% water, which 
will protect from the coil from freezing to approx-
imately -35°F at sea level. Refer to ASHRAE and 
ARI guidelines for more information.
• During winter when shutdowns such as power 
failure, night and weekend shutdowns may occur, 
install the controls so the return air dampers go to 
the fully open position, and all fresh air dampers 
go to the fully closed position. A source of aux-
iliary heat must be maintained inside the AHU 
cabinet.
• Other protection can include electromechanical 
switchesandconstantlyowingwater;however,
Johnson Controls will not be responsible for any 
coils damaged by freezing.
Steam Coils
The operation of steam coils is dependent on airflow 
quantity and temperature as shown in Figure 121 on 
page 78. Consult the job submittal form for the in-
formation specific to this AHU.
Steam Distributing Coils
Use the following instructions to clean the steam dis-
tributing coils: 
• Do not bush or reduce the coil return pipe size.
• Use a full size return pipe to the bottom of a dirt 
pocket. The supply pipe may be reduced at the 
coil connection, if necessary.  
• Install the coil casing level with the return down. 
Acoilmustbesufcientlyelevatedtoallowa12
in. minimum drop between the return connection 
on the coil and the trap. More than a two inch drop 
is required to protect the coil from freezing. The 
return main should be located below the trap. 
Steam Control
Continuous steam supply ensures long coil life and 
minimizes potential trapping, venting and freezing 
problems. A rapid cycling of the modulating steam 
supply or a frequent on-off steam supply control re-
sults in repeated thermal and piping stresses which will 
shorten the coil life.  Modulating steam control valves 
must not be oversized, and must be carefully selected.  
A substantial variation in the supply pressure will re-
quire installing a pressure-reducing valve ahead of the 
automatic control valve.
Light load operation with a modulated steam supply 
can be improved by the installation of a vacuum break-
er check valve.  An open relief line to the atmosphere 
from the return line near the coil is desirable, except on 
vacuum systems.
With a modulated steam supply, it is not practical to lift 
the condensate to an overhead return. Locate the coil 
well above the return, or provide condensate unit, or a 
boiler return trap below the coil.
Individual control valves are required on each coil in-
stalled in series with respect to airflow. When a modu-
lating steam valve supplies two or more coils in paral-
lel, with respect to airflow, the piping must be designed 
to provide uniform steam distribution to each coil.
Steam Traps
Use the following information to select the correct 
steam trap.
• Float and Thermostatic (F and T) traps are recom-
mended for all low or medium pressure applica-
tions.  
• Use thermostatic traps only for air venting, for 
outdoor applications where a F and T trap might 
be subject to freezing. 
• Use bucket traps only for a non-modulated steam 
supply. 
• Size the steam traps in accordance with the manu-
facturer's recommendations (usually several times 
thesteadystatesteamow).