206 Fault tracing
0001 Relay output 1 Change the control board or stop using
relay output 1.
0002 Relay output 2 Change the control board or stop using
relay output 2.
0003 Relay output 3 Change the control board or stop using
relay output 3.
A8A2 RO toggle warning The relay output is changing
states faster than
recommended, eg. if a fast
changing frequency signal is
connected to it. The relay
lifetime will be exceeded
shortly.
Replace the signal connected to the relay
output source with a less frequently
changing signal.
0001 Relay output 1 Select a different signal with parameter
10.24 RO1 source.
0002 Relay output 2 Select a different signal with parameter
10.27 RO2 source.
0003 Relay output 3 Select a different signal with parameter
10.30 RO3 source.
A8B0 Signal supervision 1
(Editable message text)
Programmable warning:
32.06 Supervision 1 action
Warning generated by the
signal supervision function 1.
Check the source of the warning
(parameter 32.07 Supervision 1 signal).
A8B1 Signal supervision 2
(Editable message text)
Programmable warning:
32.16 Supervision 2 action
Warning generated by the
signal supervision function 2.
Check the source of the warning
(parameter 32.17 Supervision 2 signal).
A8B2 Signal supervision 3
(Editable message text)
Programmable warning:
32.26 Supervision 3 action
Warning generated by the
signal supervision function 3.
Check the source of the warning
(parameter 32.27 Supervision 3 signal).
A8B3 Signal supervision 4
(Editable message text)
Programmable warning:
32.36 Supervision 4 action
Warning generated by the
signal supervision function 4.
Check the source of the warning
(parameter 32.37 Supervision 4 signal).
A8B4 Signal supervision 5
(Editable message text)
Programmable warning:
32.46 Supervision 5 action
Warning generated by the
signal supervision function 5.
Check the source of the warning
(parameter 32.47 Supervision 5 signal).
A8B5 Signal supervision 6
(Editable message text)
Programmable warning:
32.56 Supervision 6 action
Warning generated by the
signal supervision function 6.
Check the source of the warning
(parameter 32.57 Supervision 6 signal).
A8B6 Current limit warning Motor actual current exceeded
the limit defined in parameter
30.17 Maximum current.
Reduce the motor load. Check for any
jam or stall in motor.
Code
(hex)
Warning / Aux. code
(aux code visible only
on assistant control
panel and drive
composer)
Cause What to do
ACQ80 FW.book Page 206 Thursday, February 14, 2019 11:33 AM