Actual signals and parameters
Parameters in the Long parameter mode
Defines the maximum value for the variable ACT1 if an analog input is
selected as a source for ACT1. See parameter 4016 ACT1 INPUT. The
minimum (4018 ACT1 MINIMUM) and maximum settings of ACT1 define how
the voltage/current signal received from the measuring device is converted to
a percentage value used by the process PID controller.
See parameter 4018 ACT1 MINIMUM.
See parameter 4018 ACT1 MINIMUM.
See parameter 4018 ACT1 MINIMUM.
See parameter 4019 ACT1 MAXIMUM.
See parameter 4019 ACT1 MAXIMUM.
Activates the sleep function and selects the source for the activation input.
No sleep function selected
The function is activated/deactivated through digital input DI1. 1 = activation,
0 = deactivation.
The internal sleep criteria set by parameters 4023 PID SLEEP LEVEL and
4025 WAKE-UP DEV are not effective. The sleep start and stop delay
parameters 4024 PID SLEEP DELAY and 4026 WAKE-UP DELAY are
effective.
Activated and deactivated automatically as defined by parameters 4023 PID
SLEEP LEVEL and 4025 WAKE-UP DEV.
The function is activated/deactivated through inverted digital input DI1.
1 = deactivation, 0 = activation.
The internal sleep criteria set by parameters 4023 PID SLEEP LEVEL and
4025 WAKE-UP DEV are not effective. The sleep start and stop delay
parameters 4024 PID SLEEP DELAY and 4026 WAKE-UP DELAY are
effective.