The general parameter setting procedure in the Short parameter mode:
1. To go to the Main menu, press if the bottom line shows OUTPUT;
otherwise press repeatedly until you see MENU at the
bottom.
2. Press keys / until you see “PAr S” on the display.
3. Press . The display shows a parameter of the Short parameter mode.
4. Find the appropriate parameter with keys / .
5. Press and hold for about two seconds until the parameter value is
shown with SET under the value.
6. Change the value with keys / . The value changes faster while
you keep the key pressed down.
7. Save the parameter value by pressing .
LOC
LOC
LOC
LOC
LOC
LOC
LOC
rEF
MENU
FWD
PAr
S
MENU
FWD
9902
s
PAR
FWD
9907
s
PAR
FWD
9907
s
PAR
FWD
Enter the motor data from the motor nameplate: Note: Set the motor data
to exactly the same value
3 motor
ABB Motors
M2AA 200 MLA 4
IEC 200 M/L 55
No
Ins.cl. F
IP 55
as on the motor
nameplate. Wrong motor
settings of parameter
group 99 may result in
V
Hz kW
r/min A cos
IA/IN
t
E/s
690 Y
400 D
660 Y
380 D
415 D
440 D
50 30
50
30
50
30
50
30
50 30
60
35
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
380
V
supply
voltage
incorrect operation of the
drive.
For example, if the motor
nominal speed is 1440
Cat. no
6312/C3
3GAA 202 001 - ADA
6210/C3
IEC 34-1
180
rpm on the nameplate,
setting the value of
parameter 9908 MOTOR
NOM SPEED to 1500 rpm
results in the wrong
operation of the drive.
• motor nominal voltage (parameter 9905 MOTOR NOM
VOLT) – follow steps given above, starting from step 4.
• motor nominal current (parameter 9906 MOTOR NOM
CURR)
Allowed range: 0.2…2.0 · I
2N
A
LOC
9905
s
PAR FWD
LOC
9906
s
PAR FWD