52
Start-up and control with I/O
50
.
0
Hz
PAR
SET
FWD
60
.
0
Hz
PAR
SET
FWD
The general parameter setting procedure in the Short parameter mode:
1. To go to the Main menu, press if the bottom line shows OUTPUT;
otherwise press repeatedly until you see MENU at the
bottom.
2. Press keys / until you see “PAr S” on the display.
3. Press . The display shows a parameter of the Short parameter mode.
4. Find the appropriate parameter with keys / .
5. Press and hold for about two seconds until the parameter value is
shown with SET under the value.
6. Change the value with keys / . The value changes faster while
you keep the key pressed down.
7. Save the parameter value by pressing .
LOC
LOC
LOC
LOC
LOC
LOC
LOC
rEF
MENU
FWD
PAr
S
MENU
FWD
9902
s
PAR
FWD
9907
s
PAR
FWD
9907
s
PAR
FWD
Enter the motor data from the motor nameplate: Note: Set the motor data
to exactly the same value
3 motor
ABB Motors
M2AA 200 MLA 4
IEC 200 M/L 55
No
Ins.cl. F
IP 55
as on the motor
nameplate. Wrong motor
settings of parameter
group 99 may result in
V
Hz kW
r/min A cos
IA/IN
t
E/s
690 Y
400 D
660 Y
380 D
415 D
440 D
50 30
50
30
50
30
50
30
50 30
60
35
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
380
V
supply
voltage
incorrect operation of the
drive.
For example, if the motor
nominal speed is 1440
Cat. no
6312/C3
3GAA 202 001 - ADA
6210/C3
IEC 34-1
180
rpm on the nameplate,
setting the value of
parameter 9908 MOTOR
NOM SPEED to 1500 rpm
results in the wrong
operation of the drive.
motor nominal voltage (parameter 9905 MOTOR NOM
VOLT) follow steps given above, starting from step 4.
motor nominal current (parameter 9906 MOTOR NOM
CURR)
Allowed range: 0.2…2.0 · I
2N
A
LOC
9905
s
PAR FWD
LOC
9906
s
PAR FWD