294 Parameters
Restore defaults All editable parameter values are restored to default values,
except
• motor data and ID run results
• parameter 31.42 Overcurrent fault limit
• control panel/PC communication settings
• fieldbus adapter settings
• encoder configuration data
• application macro selection and the parameter defaults
implemented by it
• parameter 95.01 Supply voltage
• parameter 95.09 Switch fuse controller
• differentiated defaults implemented by parameters 95.20
HW options word 1 and 95.21 HW options word 2
• user lock configuration parameters 96.100…96.102.
8
Clear all All editable parameter values are restored to default values,
except
• control panel/PC communication settings
• application macro selection and the parameter defaults
implemented by it
• parameter 95.01 Supply voltage
• parameter 95.09 Switch fuse controller
• differentiated defaults implemented by parameters 95.20
HW options word 1 and 95.21 HW options word 2
• user lock configuration parameters 96.100…96.102.
PC tool communication is interrupted during the restoring.
Note: Activating this selection will restore the default settings
of the fieldbus adapter if one is connected, potentially
including settings that cannot be accessed through drive
parameters.
62
Reset all fieldbus
settings
Fieldbus adapter and embedded fieldbus interface settings
(parameter groups 50…58) are restored to default values.
This will also restore the default settings of the fieldbus
adapter if one is connected, potentially including settings that
cannot be accessed through drive parameters.
32
96.07 Parameter save
manually
Saves the valid parameter values to permanent memory. This
parameter should be used to store values sent from a
fieldbus, or when using an external power supply to the
control board as the supply might have a very short hold-up
time when powered off.
Note: A new parameter value is saved automatically when
changed from the PC tool or control panel but not when
altered through a fieldbus adapter connection.
Done
Done Save completed. 0
Save Save in progress. 1
96.08 Control board boot Changing the value of this parameter to 1 reboots the control
unit (without requiring a power off/on cycle of the complete
drive module).
The value reverts to 0 automatically.
Note: This parameter cannot be changed while the drive is
running.
0
0…1 1 = Reboot the control unit. 1 = 1
96.10 User set status Shows the status of the user parameter sets.
This parameter is read-only.
See also section User parameter sets (page 74).
-
n/a No user parameter sets have been saved. 0
No. Name/Value Description Def/
FbEq16