EasyManua.ls Logo

ABB ACS880-14 - Overall Flowchart of the Installation Process; Installing the Mechanical Accessories into a Enclosure

ABB ACS880-14
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overall flowchart of the installation process
For instructions, seeTaskStep
Installing the mechanical accessories into a en-
closure (page 141)
Install the Rittal parts and drive module mechan-
ical accessories into the enclosure
1
Connecting the power cables (page 143)
Connect the power cables to the cabling panels2
Installing the drive module into the enclos-
ure (page 146)
Install the drive module into the enclosure3
Attaching the external control unit (page 109)
Install the external control unit4
Connecting the external control unit to the drive
module (page 107)
Connect the control cables5
The component manufacturer’s instructionsInstall the remaining parts, for example, enclosure
doors, side plates, etc.
6
Installing the mechanical accessories into a enclosure
See Step-by-step drawings for an installation example of standard drive configuration in
Rittal VX25 800 mm wide enclosure (page 233) for these steps:
1. Attach the plinth to the floor.
2. Attach the enclosure frame to the plinth.
3. Make the bottom plate with 360-degree grounding entries for power cables. Attach the
bottom plate to the enclosure frame.
4. Attach the punched section to the back of enclosure frame.
5. Attach the mounting brackets to the punched section.
To install the full cabling panels to the enclosure frame (see the drawings on the next page):
1. Install the Rittal punched sections VX 8100.742 to which the output cabling panel and
the input cabling panel will be attached.
2. Attach the output cabling panel to the punched sections.
3. Install the side guides to the output cabling panel (2 screws for each guide).
4. Attach the grounding busbar to the input cabling panel.
5. Attach the input cabling panel to the punched sections.
6. Attach the input cabling panel to the side guides (2 screws for each side guide).
7.
Install the telescopic extraction and insertion ramp as shown in chapter Step-by-step
drawings for an installation example of standard drive configuration in Rittal VX25 800 mm
wide enclosure (page 233).
Installation example with full cabling panels (option +H381) 141