The instructions and technical data which concern only certain optional selections are marked
with option codes, eg, +E208. The options included in the drive can be identified from the
option codes visible on the type designation label. The option selections are listed in section
Type designation key (page 41).
Quick installation, commissioning and operating flowchart
See chapter/sectionTask
Guidelines for planning the mechanical installa-
tion (page 55)
Plan the mechanical and electrical installation and ac-
quire the accessories needed (cables, fuses, etc.).
Examine the ambient conditions, ratings, required
cooling air flow, input power connection, compatibility
of the motor, motor connection, and other technical
data.
Guidelines for planning the electrical installa-
tion (page 75)
Technical data (page 179)
Option manual (if optional equipment is included)
Moving and unpacking (page 65)
Unpack and examine the units.
Make sure that all necessary optional modules and
equipment are present and correct.
Examining the delivery (page 72)
If the drive module has been non-operational for a year
or more, the converter DC link capacitors need to be
reformed. (Reforming the capacitors (page 169))
Only intact units can be started up.
Examining the installation site (page 65)
Examine the installation site. Attach the base of the
cabinet to the floor.
Ambient conditions (page 195)
Routing the cables (page 88)
Route the cables.
Measuring the insulation (page 100)
Measure the insulation of the supply cable, the motor
and the motor cable and the resistor cable (if present).
Installing the drive module and LCL filter module into
an enclosure (page 133)
Standard drive modules
• Install the additional components into the enclosure:
for example, main disconnector, main contactor, main
AC fuses, etc..
• Install the drive module into the enclosure.
• Connect the motor cables to the drive module termin-
als.
• Connect the brake resistor and DC connection cables
(if any) to the drive module terminals.
• If the main disconnector is installed into the enclos-
ure, connect it to the drive module terminals and the
input power cabling to the disconnector.
• Connect the cables from the drive module to the ex-
ternal control unit and install the control unit into the
enclosure
Connecting the motor cables and installing the
shrouds (page 134)
Connecting the input cables and installing the
shrouds (page 135)
Connecting the external control unit to the drive mod-
ule (page 107)
Attaching the external control unit (page 109)
Manuals for any optional equipment