ABB ACS880-14 - Terminal and Entry Data for the Power Cables

ABB ACS880-14
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
US
2)
IEC
1)
Al cable typeCu cable typeAl cable typeCu cable typeACS880-
14-…
AWG/kcmilAWG/kcmilmm
2
mm
2
U
n
= 400 V
350 MCM or 2 × 2/0250 MCM or 2 × 12 × (3 × 95)2 × (3 × 50)246A-3
500 MCM or 2 × 3/0350 MCM or 2 × 2/02 × (3 × 120)2 × (3 × 70)293A-3
700 MCM or 2 × 4/0 or 3 × 2/0500 MCM or 2 × 3/03 × (3 × 95)3 × (3 × 50)363A-3
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/03 × (3 × 120)3 × (3 × 70)442A-3
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/03 × (3 × 120)3 × (3 × 70)505A-3
2 × 500 MCM or 3 × 250 MCM2 × 350 MCM or 3 × 4/03 × (3 × 150)3 × (3 × 120)585A-3
2 × 600 MCM or 3 × 300 MCM2 × 400 MCM or 3 × 4/03 × (3 × 185)3 × (3 × 120)650A-3
U
n
= 500 V
250 MCM or 2 × 13/02 × (3 × 70)1 × (3 × 120)240A-5
350 MCM or 2 × 2/0250 MCM or 2 × 13 × (3 × 70)2 × (3 × 50)260A-5
500 MCM or 2 × 3/0300 MCM or 2 × 1/03 × (3 × 70)2 × (3 × 70)302A-5
500 MCM or 2 × 3/0350 MCM or 2 × 2/03 × (3 × 70)2 × (3 × 120)361A-5
700 MCM or 2 × 4/0 or 3 × 2/0500 MCM or 2 × 3/02 × (3 × 150)3 × (3 × 50)414A-5
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/03 × (3 × 120)3 × (3 × 70)460A-5
2 × 400 MCM or 3 × 4/02 × 250 MCM or 3 × 2/03 × (3 × 120)3 × (3 × 95)503A-5
U
n
= 690 V
3/01/02 × (3 × 50)1 × (3 × 70)142A-7
4/02/02 × (3 × 50)2 × (3 × 50)174A-7
300 MCM or 2 × 1/04/02 × (3 × 70)2 × (3 × 50)210A-7
400 MCM or 2 × 2/0300 MCM or 2 × 1/03 × (3 × 50)2 × (3 × 70)271A-7
600 MCM or 2 × 4/0 or 3 × 1/0400 MCM or 2 × 2/02 × (3 × 120)2 × (3 × 50)330A-7
700 MCM or 2 × 4/0 or 3 × 2/0500 MCM or 2 × 3/02 × (3 × 150)3 × (3 × 70)370A-7
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/02 × (3 × 185)3 × (3 × 70)430A-7
1)
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top of the
other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN 60204-1 and IEC
60364-5-52). For other conditions, dimension the cables according to local safety regulations, appropriate input voltage
and the load current of the drive.
2)
The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C (104 °F) ambient
temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly buried). For other
conditions, dimension the cables according to local safety regulations, appropriate input voltage and the load current of
the drive.
Terminal and entry data for the power cables
Terminal and entry data for the power cables
4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG)Maximum accepted cable
size
M12Screw size for connecting
busbars to the drive mod-
ule input and output bus-
bars
50…75 N·m (37…55 lbf·ft)Tightening torque
Technical data 191