Fuses (IEC)
aR fuses by Cooper Bussmann for protection against short-circuit in the input power cable
of drive are listed below.
Ultrarapid (aR) fuses per drive module
FuseInput
current
(A)
ACS880-
14-…
SizeType Flush EndVA
2
sA
U
n
= 400 V
2170M540869074000400212246A-3
2170M5410690145000500257293A-3
3170M6410690210000630321363A-3
3170M6411690300000700401442A-3
3170M6412690465000800401505A-3
3170M64146909450001000505585A-3
3170M64146909450001000569650A-3
U
n
= 500 V
1170M441069042000315169240A-5
2170M540869074000400205260A-5
3170M6410690210000630257361A-5
3170M6411690300000700321414A-5
3170M6411690300000700404460A-5
3170M6412690465000800455503A-5
U
n
= 690 V
1170M440969021000250123142A-7
1170M441069042000315149174A-7
2170M540869074000400186210A-7
2170M5410690145000500232271A-7
3170M6410690210000630293330A-7
3170M6411690300000700330370A-7
3170M6411690300000700375430A-7
Note:
See also sections:
Protecting the drive and the input power cable in short-circuits (page 91)
Protecting the drive against thermal overload (page 91)
Protecting the input power cable against thermal overload (page 91).
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Fuses with higher current rating than the recommended ones must not be used. Fuses
with lower current rating can be used.
Fuses from other manufacturers can be used if they agree with the ratings and the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the table.
Technical data 187