Fuses (UL)
UL fuses by Cooper Bussman for branch circuit protection per NEC per drive module are
listed below. Obey local regulations.
Fuse
Input cur-
rent (A)
ACS880-
14-…
SizeType French StyleType US StyleType DIN 43653VA
U
n
= 500 V
1170M4310170M4610170M4010690315169240A-5
2170M5308170M5608170M5008690400205260A-5
2170M5310170M5610170M5010690500249302A-5
3170M6310170M6610170M6010690630257361A-5
3170M6311170M6611170M6011690700321414A-5
3170M6311170M6611170M6011690700404460A-5
3170M6212170M6612170M6012690800455503A-5
U
n
= 690 V
1170M4309170M4609170M4009690250123142A-7
1170M4310170M4610170M4010690315149174A-7
2170M5308170M5608170M5008690400186210A-7
2170M5310170M5610170M5010690500232271A-7
3170M6310170M6610170M6010690630293330A-7
3170M6311170M6611170M6011690700330370A-7
3170M6311170M6611170M6011690700375430A-7
Note:
See also sections:
Protecting the drive and the input power cable in short-circuits (page 91)
Protecting the drive against thermal overload (page 91)
Protecting the input power cable against thermal overload (page 91).
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Fuses with higher current rating than the recommended ones must not be used. Fuses
with lower current rating can be used.
Alternative fuses can be used if they meet certain characteristics. For acceptable fuses,
see the technical note (3AXD50000645015).