EasyManua.ls Logo

ABB ACS880-14 - Start-Up; Contents of this Chapter; Start-Up Procedure

ABB ACS880-14
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start-up
Contents of this chapter
This chapter describes the start-up procedure of the drive.
Start-up procedure
1. Only qualified electrical professionals are allowed to start-up the drive.
2. Make sure that the installation of the drive module has been checked according to the
checklist in chapter Installation checklist, and that the motor and driven equipment are
ready for start.
3. Perform the start-up tasks instructed by the cabinet-installer of the drive module.
4. Switch the power on, setup the drive control program, and perform the first start of the
drive and motor. See Quick start-up guide for ACS880 drives with primary control program
(3AUA0000098062 [English]) or ACS880 primary control program firmware manual
(3AUA0000085967 [English]). If you need more information on the use of the control
panel, see ACx-AP-x Assistant control panels user's manual (3AUA0000085685
[English]).
For drives with ABB du/dt filter: Check that bit 13 of parameter 95.20 HW options
word 1 is switched on.
For drives with ABB sine filter: Check that parameter 95.15 Special HW settings is
set to ABB sine filter. For other sine filters: See Sine filter hardware manual
(3AXD50000016814 [English]).
5.
For drives with ABB motors in explosive atmospheres: See also ACS880 drives with
ABB motors in explosive atmospheres (3AXD50000019585 [English]).