• ABB recommends 360° high-frequency grounding of the motor cable shields at their
entries. The grounding can be implemented by a knitted wire mesh screening as shown
below.
Cable1
Cable tie2
Strain relief3
Bare cable shield4
Knitted wire mesh5
Cabinet entry plate6
• ABB recommends 360° high-frequency grounding of the control cable shields at their
entries. The shields can be grounded by means of conductive shielding cushions pressed
against the cable shield from both directions as shown below.
Tightening screw1
EMI conductive cushion2
Strain relief3
Grommet4
Entry plate5
Attaching the cabinet
WARNING!
Do not attach the cabinet by electric welding. ABB does not assume any liability
for damages caused by electric welding as the welding circuit can damage
electronic circuits in the cabinet.
Generic cabinet planning instructions 51