With other than recommended sine filters (see section Sine filters (page 232)) and non-ABB
Ex motors, contact ABB.
Output ratings for special settingsACS880-
14-…
Low noise modeABB sine filterEx motor (ABB Ex motor)
Heavy-
duty
use
Light-
duty
use
Nominal useHeavy-
duty
use
Light-
duty
use
Nominal useHeavy-
duty
use
Light-
duty
use
Nominal use
I
Hd
I
Ld
P
n
I
n
I
Hd
I
Ld
P
n
I
n
I
Hd
I
Ld
P
n
I
n
AAkWAAAkWAAAkWA
U
n
= 400 V
180204132217185210132221196222132234246A-3
215243160258221251160264234264160278293A-3
256301200320264310200327278328200345363A-3
317367250390327378250398345399250420442A-3
317419250445327432250455345456315480505A-3
386485315516398500315527420528315556585A-3
441539315573455556355585480587355618650A-3
U
n
= 460 V
277264250 hp266234272250
hp
272247287250
hp
287302A-5
U
n
= 500 V
157199132212162205132216171217132228240A-5
210216160229216222160234228235160247260A-5
227300200318234309200325247326200343361A-5
315343250365325354250373343373250393414A-5
362393250406373405315414393428315437460A-5
402430315443414443315453437467355478503A-5
U
n
= 690 V
55637566107122132128105119132125142A-7
66779081128149160157125145160153174A-7
819311098157180200189153176200185210A-7
98119132126189231250244185226250238271A-7
126149160154244288315297238282315290330A-7
153167200172297324355333290317355326370A-7
172195200200333378400387326370400378430A-7
Nominal voltage of the drive
U
n
Continuous rms output current. No overload capability at 40 °C (104 °F)
I
n
Typical motor power in no-overload use
P
n
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I
Ld
Typical motor power for light-duty use
P
Ld
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
I
Hd
Technical data 183