PROFIdrive parameters
124
927 R/W Unsigned16 Operator control rights (parameter identification, PKW).
Value Mode
0 Parameters cannot be written, only read
(927 can be written)
1 Parameters can be written and read
(default).
928 R/W Unsigned16 Control rights (process data, PZD).
Value Mode
0 PZD part is disabled, i.e. Receipt of new
PZD data is ignored
1 PZD part is enabled (default).
929 R Unsigned16 Selected PPO type
Value PPO type Configuration
1 PPO1 F3h, F1h
2 PPO2 F3h, F5h
3PPO3 F1h
4PPO4 F5h
5 PPO5 F3h, F9h
6PPO6 F9h
Note: This parameter is not available if Standard telegram
ST1 or ST2 is selected.
930 R/W Unsigned16 Selection switch for communication profile.
Value Mode
1 PROFIdrive
8001h ABB Drives
8002h Transparent 16
8003h Transparent 32
8004h PROFIdrive positioning mode
933 R/W Unsigned16 Selection switch for Control word, bit 11.
Value Module Control word bit
0 None
1 to 5 Vendor specific 1 to 5*
* The meaning of vendor specific bits is defined by drive
application program.
Param-
eter
R/W
*
Data type Description