PROFIdrive parameters
125
934 R/W Unsigned16 Selection switch for Control word, bit 12. (See parameter
933 for coding)
935 R/W Unsigned16 Selection switch for Control word, bit 13. (See parameter
933 for coding)
936 R/W Unsigned16 Selection switch for Control word, bit 14. (See parameter
933 for coding)
937 R/W Unsigned16 Selection switch for Control word, bit 15. (See parameter
933 for coding)
939 R/W Unsigned16 Selection switch for Status word, bit 11.
Value Module Status word bit
0 None
1 to 4 Vendor specific 1 to 4*
* The meaning of vendor specific bits is defined by drive
application program.
940 R/W Unsigned16 Selection switch for Status word, bit 12. (See parameter
939 for coding)
941 R/W Unsigned16 Selection switch for Status word, bit 13. (See parameter
939 for coding)
942 R/W Unsigned16 Selection switch for Status word, bit 14. (See parameter
939 for coding)
943 R/W Unsigned16 Selection switch for Status word, bit 15. (See parameter
939 for coding)
945 R Array[64]
Unsigned16
Fault code (coded according to DRIVECOM profile).
Note: The drive may limit the actual number of faults
recorded.
Subindex Contents
1 Active fault
9 **Last ackn. fault
17 **Second last ackn. fault
25 **Third last ackn. fault
33 **Fourth last ackn. fault
41 **Fifth last ackn. fault
947 R Array [64]
Unsigned16
Fault number.
Subindex Contents
See parameter 945.
Param-
eter
R/W
*
Data type Description