FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E 87
Submenu Set the time-out limits and alarm behavior for values over or
under the coil temperature.
Notice: To correctly display the coil resistance or coil
temperature, an adjustment is required or the cable length
must be entered. For additional information, see ‘Submenu
Adjustment’ on page 93.
Min. value -100 ... 200 Lower range limit for alarm.
-50 °C
Max. value -100 ... 200 Upper range limit for alarm.
200 °C
Message Off, warning, error Defines the alarm behavior.
Notice: If coil resistance is being measured (at least every 60
s), the most recently acquired flow rate is retained during the
measurement (2 s approx.).
Set the time-out limits and alarm behavior for values over or
under the coil temperature.
Alarm Ins Resist
Lower range limit for alarm.
Upper range limit for alarm.
Off, warning, error
Defines the alarm behavior.
Off Notice: If coil insulation resistance is being measured (at least
every 10 minutes), the most recently acquired flow rate is
retained during the measurement (2 s approx.).