480 Verification and validation
2. Make sure that you can ran and stop the motor freely.
3. Start the drive and accelerate to a speed higher than the SMS limit
positive (200.73).
4. Make sure that SMS function limits the motor speed to the required limit by the
application. Try to give a speed reference higher than the limit. Make sure that the
drive does not follow speed reference if it is higher than the SMS limit. Repeat the
test for both SMS limits (if in use in the application).
5. Make sure that also SMS trip limits (200.72, 200.73) are set according to the
application requirements. This procedure does not test the trip limits.