110 1SFC132003M0201
)LHOGEXVFRPPXQLFDWLRQRSWLRQ
&KDSWHU
34 Read/Write PTC Op Type of operation for PTC protection Stop–M, Stop–A, Ind
35 Read/Write Ext ByPass External By-pass contactor is used No, Yes
36 Read/Write BP Fault Op Type of operation for by-pass moni-
tor protection
Stop–M, Stop–A
37 Read/Write Warn I=High High current warning No, Yes
38 Read/Write Wa I=H Lev Trip level for high current warning 0,5 – 5,0 x Ie
39 Read/Write Warn I=Low Low current warning No, Yes
40 Read/Write Wa I=L Lev Trip level for low current warning 0,4 – 1,0 x Ie
41 Read/Write Warn OL Overload warning No, Yes
42 Read/Write Wa OL Lev Trip level for overload warning 40 – 99 %
43 Read/Write Warn SCR OL Thyristor overload warning No, Yes
44 Read/Write Ph Loss Op Type of operation for phase loss
fault
Stop–M, Stop–A
45 Read/Write FB Fault Op Type of operation for fieldbus fault Stop–M, Stop–A
46 Read/Write Freq F Op. Type of operation for frequency fault Stop–M, Stop–A
47 Read/Write HS Temp Op Type of operation for heat sink over
temperature fault
Stop–M, Stop–A
48 Read/Write SCR SC Op Type of operation for thyristor short
circuit fault
Stop–M, Stop–A
49 Read In0 Function of programmable input In0 None, Reset, Enable,
Jog, DOL-on, Start2
50 Read In1 Function of programmable input In1 None, Reset, Enable,
Jog, DOL-on, Start3
51 Read/Write Relay K4 Function of programmable relay out-
put K4
Run, TOR, Event
52 Read/Write Relay K5 Function of programmable relay out-
put K5
Run, TOR, Event
53 Read/Write Relay K6 Function of programmable relay out-
put K6
Run, TOR, Event
54 Read/Write SW Outp V7 Function of programmable software
output V7
Run, TOR, Event
55 Read/Write Event K4 Different events to include for signal-
ling with K4 if “Event” is selected
0 – 65535, Bit mask
see separate
description.
56 Read/Write Event K5 Different events to include for signal-
ling with K5 if “Event” is selected
0 – 65535, Bit mask
see separate
description.
57 Read/Write Event K6 Different events to include for signal-
ling with K6 if “Event” is selected
0 – 65535, Bit mask
see separate
description.
58 Read/Write Event V7 Different events to include for signal-
ling with V7 if “Event” is selected
0 – 65535, Bit mask
see separate
description.
59 Read Fieldb Ctrl Control of the softstarter with field-
bus
No, Yes
60 Read Fieldb Type Type of fieldbus AS-I, Other
61 Read Fieldb Addr Fieldbus address 0 – 1000
1R 7\SH 3DUDPHWHU 'HVFULSWLRQ 5DQJH 8QLW