EasyManua.ls Logo

ABB PST Series - 4:2.4 Minimum enclosure sizes

ABB PST Series
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
1SFC132003M0201
0RXQWLQJ
&KDSWHU
 0LQLPXPHQFORVXUHVL]HV
In applications where the softsarter is installed in an
enclosure, the following minimum enclosure sizes and fan
capacities are recommended.
(1mm = 0,0394 in)
'LPHQVLRQVDQGGULOOLQJSODQ
See Chapter 3 “Description” .
0LQLPXPHQFORVXUH
GLPHQVLRQV
6RIWVWDUWHUW\SH : + ' )DQFDSDFLW\
PST30...72 300 400 250 42 m
3
/h
PST85...142 400 500 300 95 m
3
/h
PST175...300 500 600 300 210 m
3
/h
PSTB370...470 600 600 400 210 m
3
/h
PSTB570...1050 750 900 400 210 m
3
/h

Table of Contents