ABB PST Series - 10:28 Phase imbalance protection, type of operation

ABB PST Series
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
133
1SFC132003M0201
)XQFWLRQV
&KDSWHU
 3KDVHLPEDODQFHSURWHFWLRQW\SH
RIRSHUDWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV3KDVH,PE3KDVH,PE2S
This parameter makes it possible to select between three
different actions of the softstarter when the protection is
activated. It is active only if the phase imbalance
protection is selected.
 +LJKFXUUHQWSURWHFWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV+LJK,
This is a current protection with a fixed level of 8 x Ie
during 200 ms. The protection is activated if the current
exceeds this level and time.
Stop–M The motor stops and a manual reset is
required before restart.
Stop–A The motor stops and an automatic reset is
performed when the fault disappears.
Ind The motor continues to run but a fault indi-
cation is given.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Ph Imb Op Stop–M Stop–M, Stop–A,
Ind
High current pro-
tection
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
High I No Yes, No High current pro-
tection