132 1SFC132003M0201
)XQFWLRQV
&KDSWHU
 3KDVHLPEDODQFHSURWHFWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV3KDVH,PE
If the current in one phase differs from another phase with
more than the set level the protection is activated.
The protection starts monitoring 30 seconds after full
voltage
.
 3KDVHLPEDODQFHSURWHFWLRQOHYHO
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV3KDVH,PE3K,PE/HY
This parameter makes it possible to set the level of the
phase imbalance protection. It is active only if the Phase
imbalance protection is selected.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Phase Imb No Yes, No Phase imbal-
ance protection
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Ph Imb Lev 80% 10...80% Trip level for
Phase imbal-
ance protection