127
1SFC132003M0201
)XQFWLRQV
&KDSWHU
 2YHUORDGFODVVGXDOW\SHUXQ
FODVV
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV2YHUORDG'XDO&ODVV5
This parameter makes it possible to set the required class
of the overload protection for continuous run. The run
class is activated 30 seconds after full voltage has been
reached.
 2YHUORDGSURWHFWLRQW\SHRI
RSHUDWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV2YHUORDG2/2S
This parameter makes it possible to select between three
different actions by the softstarter when the protection is
activated. It is active only if the motor overload protection
is selected.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
OL Class R 10 10A, 10, 20, 30 Overload class,
Dual type, Run
Class
Stop–M The motor stops and a manual reset is
required before restart.
Stop–A The motor stops and an automatic reset is
performed when the fault disappears
Ind The motor continues to run but a fault indi-
cation is given.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
OL Op Stop–M Stop–M, Stop–A,
Ind
Type of opera-
tion for over-
load protection