127
1SFC132003M0201
)XQFWLRQV
&KDSWHU
2YHUORDGFODVVGXDOW\SHUXQ
FODVV
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV2YHUORDG'XDO&ODVV5
This parameter makes it possible to set the required class
of the overload protection for continuous run. The run
class is activated 30 seconds after full voltage has been
reached.
2YHUORDGSURWHFWLRQW\SHRI
RSHUDWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV2YHUORDG2/2S
This parameter makes it possible to select between three
different actions by the softstarter when the protection is
activated. It is active only if the motor overload protection
is selected.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
OL Class R 10 10A, 10, 20, 30 Overload class,
Dual type, Run
Class
Stop–M The motor stops and a manual reset is
required before restart.
Stop–A The motor stops and an automatic reset is
performed when the fault disappears
Ind The motor continues to run but a fault indi-
cation is given.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
OL Op Stop–M Stop–M, Stop–A,
Ind
Type of opera-
tion for over-
load protection