The sequence start function can be used for starting
several motors or multiple speed motors with different
parameter sets such as individual ramp times, initial
voltages, current limits etc.
Up to three individual parameter sets can be used
simultaneously.
7KH/2&$/&21752/PHQXFDQQRWEHHQWHUHGLI
6HTXHQFHVWDUWLVVHOHFWHG
1XPEHURIVHTXHQFHV1RRI6HT
To set parameters related to a sequence start, enter the
Seq Start group.
Select the required number of parameter sets for the
application.
The following selections are available:
No Sequence start is not activated.
The softstarter is in normal operation.
2 Two different parameter sets will be used.
3 Three different parameter sets will be used.
Press 6WRUH to save/activate the selected function.
)LUVWVHTXHQFHVHWWLQJFXUUHQWVW6HW,H
Set the current for the first parameter group and press
6WRUH to save the value.
This parameter will only be displayed if parameter
1RRI6HT is set to 2 or 3.
6HFRQGVHTXHQFHVHWWLQJFXUUHQWQG6HW,H
Set the current for the second parameter group.
Press 6WRUH to save the value.
This parameter will only be displayed if parameter
1RRI6HT is set to 2 or 3.