This parameter makes it possible to set the delay time
from detection until activation of the protection.
It is active only if Locked rotor protection is selected.
/RFNHGURWRUSURWHFWLRQW\SHRI
RSHUDWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV/RFNHG5RWRU/RFN52S
This parameter makes it possible to select between three
different actions of the softstarter when the protection is
activated. It is active only if the Locked rotor protection is
selected.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Lock R
Time
1,0 s 0,2...10,0 s Trip time for
locked rotor pro-
tection
Stop–M The motor stops and a manual reset is
required before restart.
Stop–Ind The motor stops and an automatic reset is
performed when the fault disappears
Ind The motor continues to run but a fault indi-
cation is given.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Lock R Op Stop–M Stop–M, Stop–A,
Ind
Type of opera-
tion for locked
rotor protection