The time of the start ramp is settable up to 30 seconds as
default, but if required the range could be extended up to
120 seconds by this parameter.
$WRRORQJUDPSWLPHZLOOLQFUHDVHWKHULVNRIWULSSLQJWKH
RYHUORDGSURWHFWLRQ
 6WRSUDPSUDQJH
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
6WDUW6WRS6WRS5DQJH
The time for the stop ramp is settable up to 30 seconds as
default, but if required the range could be extended up to
120 seconds by this parameter.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Start Range 1-30 s 1-30 s, 1-120 s Selectable
range for start
ramp
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Stop Range 0-30 s 0-30 s, 1-120 s Selectable range
for stop ramp