ABB PST Series - 11:4 Fault indication

ABB PST Series
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
161
1SFC132003M0201
7URXEOHVKRRWLQJ
&KDSWHU
 )DXOWLQGLFDWLRQ
6WDWXV 3RVVLEOHFDXVH 6ROXWLRQ
3KDVHORVVIDXOW The main contactor or circuit
breaker is open.
Fuse blown.
Any external device open /
tripped.
Check and close contactor / breaker or
any external switching device.
Check and replace the fuse in all three
(3) phases.
&RQQHFWLRQIDXOW The motor connection is not
correct.
Shorted thyristor at start.
Shorted thyristor at start.
,Q/LQHFRQQHFWHG
Check that there are no connections
missing to the motor.
Check that the connections are carried
out correctly.
Check and replace.
,QVLGH'HOWDFRQQHFWHG
Check that there are no connections
missing to the motor.
Check that the circuits are closed and
correspond to the circuit diagram.
Check and replace.
)UHTXHQF\IDXOW The frequency is out of range.
(47,5 - 52,5Hz or 57 - 63Hz)
Check and correct the frequency.
/LQHVLGH)DXOW The main voltage is not correct
on the line side.
Check and correct voltage on the line
side.
Power on ProtectionFault
(CWNV2JCUG.QUU
4GUGV $CEM
Power on ProtectionFault
(CWNV%QPPGEVKQP
4GUGV $CEM
Power on ProtectionFault
(CWNV9TQPI(TGS
4GUGV $CEM
Power on ProtectionFault
(CWNV.KPG5KFG
4GUGV $CEM