85
1SFC132003M0201
6HWWLQJVDQGFRQILJXUDWLRQ
&KDSWHU
6HFRQGSURJUDPPDEOHLQSXW,Q
Select the required function for the input In1.
One of the following functions can be selected:
None No specific function (not activated).
Reset Reset of a fault or overload condition.
Enable When the In1=0 the softstarter stops
immediately.
When In1=1 the softstarter is in normal
operation.
Overrides all other inputs.
Jog Performs a start ramp until command is
released, then the motor stops immediately.
DOL Open/close of the by-pass contactor
(PSTB370...PSTB1050).
Start3 Start signal for 3rd parameter set-up.
Press 6WRUH to save/activate the selected function.