Syntax: lis rec
Description
This command is used to list all the rectifiers in the system. The command will list all present and
missing rectifiers. Missing rectifiers are rectifiers that have been removed from a shelf. The cle will
clear missing rectifiers from the controller's memory and they will no longer be listed by this command.
Return value for a system with 3 rectifiers on shelf 1 would look like the following:
lis rec
G11
G12
G13
.
_
Syntax: login password
where password is either the user, super-user or administrator password
Description
This command is used to log-in as a user, super-user or administrator. For example, if you are currently
logged into the controller as a user but would like to change the site id you
must first use this command to log-in as a super-user. You must be logged in as an administrator in
order to upgrade the software and change passwords.
Syntax: ope obj,attr=value
where: obj,attr is an object-attribute pair. For example, dc1,pbt.
Description
This command is used to operate a system control parameter. Examples are listed below to illustrate
how this command works.
ope ps1,usl=1Update serial link
ope dc1,stt="boost"Place plant into boost mode
You must be logged in as a super-user to use this command.
Lis List Rectifiers
Login Log– in
Ope Operate a Control