This report gives the start date, start time, start reason, stop reason, and boost duration in minutes.
The start reasons are:
MANUALBoost initiated by user
AUTOBoost started automatically after a battery discharge RESUMEDBoost resumed after being
suspended by a discharge
The stop reasons are:
COMPLETEDBoost completed normally TIMEOUTBoost timed out before completing
DISCHARGEBoost suspended because of a battery discharge CANCELED Boost canceled by user
ALARMBoost cancelled by an alarm condition
DISABLEDAuto boost cancelled by being disabled
Syntax: dc1,bod
Description
This command reports the battery discharge history in the following format: his dc1,bod
30-MAY-03,15:11:12,MANUAL,COMPLETED,118.3,23,
01-APR-03,03:11:12,BD,COMPLETED,118.3,26,130
12-FEB-03,12:00:02,PERIODIC,COMPLETED,120.9,27,135
.
**
This report gives the start date, start time, start reason, current at start of discharge, duration in
minutes, and, if calculated, a reserve time prediction. The start reasons are:
MANUALDischarge test initiated by user PERIODICPeriodic discharge test BDNatural battery discharge
The stop reasons are:
COMPLETEDDischarge completed normally
TIMEOUTAuto discharge test timed out
DISABLEDAuto discharge test disabled ENDVDischarge test hit end voltage
CANCELEDDischarge test canceled by user
His Report BD History