Syntax: sum obj,attr
where: obj,attr is an object-attribute pair defined by the following:
sum dc1,adcReport plant load current statistics
sum br1,hbtReport highest battery temperature statistics
sum br1,amtReport ambient temperature statistics
Description
This command reports the highest hourly a averages, highest hourly maximum, and the highest hourly
minimum statistics for plant load and highest battery temperature. The following is an example of a
command response:
* sum dc1,adc
:DC1 ADC HHI=
30-MAY-03,12:03:00,127.3
14-FEB-03,11:15:37,126.9
24-DEC-03,02:30:13,126.2
LHI=
29-MAR-03,10:43:00,120.0
04-APR-03,11:15:53,121.1
21-SEP-03,07:13:10,124.3
HHA=
03-JAN-03,12:00:00,127.0
18-APR-03,11:00:00,126.5
21-OCT-03,02:00:00,126.1
.
*
The line “:DC1 ADCindicates that the information that follows is for the plant load current. The HHI=
indicates highest hourly instantaneous reading. The LHI= indicates highest hourly instantaneous
reading. The HHA= indicates highest hourly average reading. The “.” line is the end-of-command
identifier. The “* ” in the example above is the user command
line prompt.