EasyManua.ls Logo

ABB Pulsar Edge - Page 152

ABB Pulsar Edge
202 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 152
© Copyright 2021 ABB. All rights reserved.
Syntax: sum dc1,bod
Description
This command reports the last battery discharge profile report. The report includes cleared date and
time, start date and time, end date and time, duration in seconds, and up to 50 sample points. Each
sample is time stamped in seconds. We compress the samples to derive a minimum set of data
required to reconstruct the curve while retaining important coup de fouet minimum and maximum
voltages and lowest voltage at end of discharge.
The following is an example of a command response:
* sum dc1,bod
:DC1 BOD
CLR=29-JUN-04,10:27:11 BEG=30-JUN-04,10:38:36 END=30-JUN-04,10:42:53 DUR=256
VAL= 0,51.08
8,50.18
18,49.24
20,48.87
248,48.36
252,49.76
254,50.84
256,51.13
.
*
The “.” line is the end-of-command identifier. The “* in the example above is the user command line
prompt.
Syntax: GUI
Description
This command is for internal use only. It reports an EasyView compatibility number. The command
response is: 841GUI=1.0
sum Report Battery Discharge Statistics (profile)
GUI Report GUI Compatibility

Table of Contents