Table 166: Implementation table
OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with)
Object
number
Variation
number Description Function codes (dec) Qualifier codes (hex)
Function codes
(dec)
Qualifier codes
(hex)
1 0 Binary
input – any
variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
1
1 (default)
1)
Binary
input
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2)
1 2 Binary
input with
status
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2)
2 0 Binary
input
change –
any
variation
1 (read) 06 (no range, or all)
07, 08 (limited qty)
2 1 Binary
input
change
without
time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
2
2
1)
Binary
input
change
with time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
2 3 Binary
input
change
with
relative
time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
10 0 Binary
output
status –
any
variation
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
10 1 Binary
output
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2)
12 1 Control
relay
output
block
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
17, 28 (index) 129 (response) echo of request
30 0 Analog
input - any
variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
30 1 32-bit
analog
input
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2)
Table continues on next page