PTH PRESSURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
D - 3
Enter a day and press . Enter a month and
press . Enter a year and press .
This date can represent the creation date of the con-
figuration, the date the device or element was
installed, or some other significant date.
Select LINEAR.
In this example FUNC GENERATOR is chosen as an
output. Specify five input and output points as a per-
centage of input. The first and last points on the
curve are fixed at 0.00% and 100.00%. The 5 points
are to be between these values.
NOTE: Other output type selections not shown here
include LINEAR, SQUARE ROOT, VOL./ SPHERE
and VOL./CYLINDER.
Use
to return to a previous configuration
screen from any screen in the configuration process.
Select an output action.
Enter a value between 0 and 32 seconds.
Select an engineering unit best suited for the
application.
Input lower range value using the arrow keys, then
press . Input the upper range value.
Key Display Comments
ENTER
ENTER
DATE:
DAY: nn
MONTH: nn
YEAR: nn
ENTER
ENTER ENTER
ENTER
OUTPUT TYPE
→ LINEAR
SQUARE ROOT
3/2 FLOW MODE
BACK
ENTER
OUTPUT ACTION:
→ NORMAL
REVERSE
ENTER
DAMPING:
(0 - 32 SEC)
_ n.nn SECS
ENTER
ENGINEERING UNIT
→ iH20 mmH2O mmHg
PSI BARS mBAR
Kgcm
2
KPA
ENTER
LOWER RANGE VAL
nn.nn UNITS
UPPER RANGE VAL
nn.nn UNITS
ENTER