XM/SM/XE MAGNETIC FLOWMETER
CREATE/MODIFY CONFIGURATION
I - 3
Enter a value between 0 and 32 seconds.
Select required engineering units.
NOTE: If not using User Defined engineering units
skip the next five screens to RANGE VALUES.
Enter the description of the user defined engineering
units.
Enter a range and a scale factor for the user defined
engineering unit.
Select a time relation for the user defined engineer-
ing unit.
If the engineering unit is not mass related, skip the
next screen.
Enter the density factor for the user defined engi-
neering unit.
Input range value 1 using the number keys, then
press . Input range value 2. The UNITS
displayed will be those designated in the previous
screens.
Key Display Comments
ENTER
DAMPING:
(0 - 32 SEC)
_nn.nn SEC
ENTER
SELECT PV EU
→ I/s
l/m
User Defined
ENTER
EU DESCRIPTOR:
nnnn
ENTER
EU FACTOR:
nnn.nn EU/l
ENTER
TIME RELATION
→ PER SEC
PER MIN
PER HOUR
ENTER
EU MASS RELATED?
→ NO
YES
ENTER
DENSITY FACTOR:
(0.1 - 5 g/cm
3
nnn.nn
ENTER
RANGE VAL 1:.
nnn.nn UNITS
RANGE VAL 2:
nnn.nn UNITS
ENTER