77
9. Display Menu
Information screens and %RH and °C setpoint screens
Frontpage w. status
-Airtec Ext.Box-
Software V. 2.00
Ty pe: 3x%RH
St atus: OK
Ext. Stop Active
Startup screen - with software version no. and status.
Type: 3x%RH or 2x%RH/°C.
Status: OK or ALARM.
Ext. Stop Active: Shown if external stop is activated.
%RH - zone XX
Z: XX Closed
Actual 52%RH
Set. 50%RH
Z: XX Open
Actual 47%R H
Set. 50%RH
or
%RH/°C - zone XX
Z: XX Open
Actual 47%R H
Set. 50%RH
Actu al 25°C
Set. 20°C
Zone overview %RH/Setpoint.
Z: XX...
Actual..%RH
Set.......%RH
Z: XX...
Actual..%RH
Set.......%RH
Actual......°C
Set...........°C
Zone no. and info if valve is Open or Closed.
Actual humidity in zone.
Humidity setpoint for zone.
Zone no. and info if valve is Open or Closed.
Actual humidity in zone.
Humidity setpoint for zone.
Actual temperature in zone.
Temperatur setpoint for zone.
To change setpoints, goto password screen and enter password.
Soaking/o delay time
Soaking Time/
O del Ex.Start
Zone: Ti m e:
X1 00:00h°
X2 00:00 m
X3 00:00s°
Soaking time/o delay ext. start - time setup. Only visible if enabled.
The time signature can be changed to: h: hh:mm, m: mm:ss, s: ss:00.
The symbol ” ° ” means that soaking/o delay is enabled.
Puls/pause will be disabled, if the zone ----is setup as sensor controlled
To change setpoints, goto password screen and enter password.
Password
Type Password
to enter setup
Password:
001300
Page to access setup menu, password protected:
Password User setup: 1300.
Maintenance: 9963.
When typing the password, the user setup menu will be available
for 10 min. then the menu will be hidden again, this is to prevent
unauthorized access.
1/9 Inputs
I:
1
/9
1
2
3456
7
89
10+ 0123456789
20+
01234
Information on ditial input - screen 1/9.
If a input is ”ON” the number of the input gets black:
3x%RH. 2x%RH/°C .
I7 = Ext. start 1
st
zone. Ext. start 1
st
zone.
I8 = Ext. start 2
nd
zone.
I1 = Ext. start 3
rd
zone. Ext. start 2
nd
zone.
I5 = Ext. stop. Ext. stop.
I6= Alarm in. Alarm in.
2/9 Outputs
Q:
2
/9
1
2
3
456789
10+ 0123456789
20+
01234
Information on output - screen 2/9.
If an output is ”ON” the number of the output gets black .
Q1 = 1
st
or 2
nd
or 3
rd
zone is active.
Q2 = Valve 1
st
zone is open.
Q3 = Valve 2
nd
zone is open.
Q4 = Valve 3
rd
zone is open.
3/9 Analog inputs
AI: 3/9
1: 000000
2: 000489
3: 000000
4: 000000
5: 000000
Information on analog input - screen 3/9.
On this page you can read the analog input values.
3x%RH. 2x%RH/°C.
AI1 = %RH 1
st
zone. %RH 1
st
zone.
AI2 = %RH 2
nd
zone. °C 1
st
zone.
AI3 = %RH 3
rd
zone. %RH 2
nd
zone.
AI4 = °C 2
nd
zone.
0-100 %RH = 0 - 1000. -40 - 60 °C = 0 - 1000.
9/9 Arrow screen
ESC+C.. 9/9
~
| }
Arrow screen 9/9:
[ESC] +
[ESC] + ~
Reset all alarms, soaking and o delay ext. start.
Start soaking for all zones activated for this.
Maintenance setup screens.
Software/rst zone no.
Software 3x%RH
0=%RH
1=%R H/°C 0
First Zone No.
1
Software control type selection:
Sof...3x%RH
Type
First Zone
No..
Changes depending on the type.
Select 0 for %RH or 1 for %RH/°C.
It is possible to change the rst zone no., and then the
others will get the numbers after.
Zone control
-Zone Control-
0=O 2=Ex+Hyg
1=%R H 3=E x-Hyg
Z: X1 1
Z: X2 2
Z: X3 0
Setup of control method:
Control methods:
0 = O Deactivated.
1 = %RH or /°C Room sensor %RH or %RH/°C, 0-10 V DC.
2 = Ex+Hyg External start signal with hygiene +24 V.
3 = Ex-Hyg External start signal no hygiene +24 V.
External stop
-Ext.Sto p 1=Yes
Z: X1 1
Z: X2 0
Z: X3 0
NO =0,NC=1 0
Delay,Sec. XX
Setup of external stop.
Change to 1 of you want the zone to stop on the ext. stop signal (I5).
NO or NC Normally open = 0, Normally closed = 1.
Delay Delay in sec. before start after external stop.
Sensor oset
-Sensor Oset-
Zone: Oset:
XX X%RH
XX -X%RH
XX X%RH
Sensor oset
Change the value to the oset you want to change it to minus, put in
a value, then change the ”+” to ”-”
Alarm limit %RH/hysteresis
-Alarm Limit %RH
Low %RH XX
High %RH XX
-Hysteresis-
%RH X
°C X
Setup of %RH alarm limits and hysteresis:
Low Zone low limit (default 10 %RH).
High Zone high limit (default 80 %RH).
%RH Setpoint + hysteresis = startpoint for humidication.
°C Setpoint + hysteresis = startpoint for humidication.
Alarm in / hygiene rinse
-Ext. Alarm IN-
NO =0,NC=1 0
Delay, Sec. 10
-Hygiene Rinse-
Rin se,Se c. 20
Between,H. 6
Setup of alarm in NO/NC and hygiene rinse time.
NO=0,NC=1 Alarm In normaly open/closed.
Delay, Sec. Delay before alarm in.
Rinse, Sec . Hyhine rinse time.
Between, H. Time between hygiene rinse.
Popup - information screen - are only visible when soaking or o delay ext. start is active.
Info. soaking/o delay
Info. Soaking/
O del Ext.Start
Zo n e: T.le f t
X1 00:00h
X2 00:00h
X3 00:00h
Info. screen - soakinf/o delay ext. start is active.
Information that soaking/o delay ext. start is active and
information on the remaining time.
Can be stopped on the ”Arrow screen” pressing
[ESC] +
The time signature means: h: hh:mm, m: mm:ss, s: ss:00.
201218