9. Display Menu
Alarm screens - are only visible when an Alarm is active.
High %RH alarm
-High %RH Alarm-
Z: XX YES
Z: XX NO
Z: XX NO
Information that high %RH alarm is active.
Zone with high %RH alarm will display YES.
Cause: Solution:
%RH above alarm limit. Check %RH setpoint.
Shorted sensor or cable. Replace sensor or cable.
Defect zone valve, not closing. Replace zone valve.
Low %RH alarm
-Low %RH Alarm-
Z: XX YES
Z: XX NO
Z: XX NO
Information that low %RH alarm is active.
Zone with low %RH alarm will display YES.
Cause: Solution:
%RH below alarm limit. Check %RH setpoint.
Broken sensor/wire connection. Replace sensor/check wire.
Defect zone valve, not opening. Replace zone valve.
Alarm in
-Alarm IN-
Alarm IN
is
Active
Information that alarm in is active.
Shared user and maintenance setup screens.
Puls/pause
-Puls/Pause-
Zone: X X
20/ 10sec
Zone: X X
15/ 0sec
Puls/pause setup.
XX/ XX Puls / pause time in sec.
If pause = 0 then the zone will be constant spraying.
Enable soaking/o delay
Enable Soaking/
O del Ex.Start
Zone: En a ble =1
X1 1
X2 0
X3 1
Enable soaking / o delay ext. start.
Disabled = 0. Enabled = 1.
If the zone uses Sensor this will work as soaking (no pulsing).
When started, the zone wil spray water for the required time.
If the zone is ext. started this works as an o delay, when start signal
is given the zone wil spray water for the required time.
Hours
-Zone Hours-
Z: X1 hhhhhh
Z: X2 hhhhhh
Z: X3 hhhhhh
Zone hours:
hhhhhh Hours the zone has been open.
With User password, read only.
Log
-LOG-
PowerUp XXXXXX
Alarm IN XXXXXX
Low %RH XXXXXX
High %RH XXXXXX
Reset=1 0
Power up and alarm log:
Info about how many times an alarm has appeared.
Reset=1. Reset Log, change 0 to 1.
Only possible with 9963 password.