122 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
JamWarningLevel
This parameter determines the Jam
Warning Level as a percentage
of Full Load Amps.
Parameter Number 73
Access Rule GET
Data Type UINT
Group Advanced Config.
Units %FLA
Minimum Value 50
Maximum Value 600
Default Value 150
StallEnabledTime
This parameter determines the time
that stall detection is enabled during
motor starting.
Parameter Number 74
Access Rule GET
Data Type USINT
Group Advanced Config.
Units secs
Minimum Value 0
Maximum Value 250
Default Value 10
StallTripLevel
This parameter determines the Stall Trip
Level as a percentage of Full Load Amps.
Parameter Number 75
Access Rule GET
Data Type UINT
Group Advanced Config.
Units %FLA
Minimum Value 100
Maximum Value 600
Default Value 600
ULInhibitTime
This parameter determines the time
during motor starting that Underload
detection is inhibited.
Parameter Number 76
Access Rule GET
Data Type USINT
Group Advanced Config.
Units secs
Minimum Value 0
Maximum Value 250
Default Value 10

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ArmorStart 294E and is the answer not in the manual?

Allen-Bradley ArmorStart 294E Specifications

General IconGeneral
BrandAllen-Bradley
ModelArmorStart 294E
CategoryController
LanguageEnglish

Related product manuals