146 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
Advanced Configuration
SetToDefaults
This parameter if set to “1” will set the
device to the factory defaults.
0 = NoAction
1 = SetToDefaults
Parameter Number 68
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
AccelTime2
When active, sets the rate of acceleration for all speed increases except for jog.
Parameter Number 69
Related Parameters 36
Access Rule GET/SET
Data Type UINT
Group Advanced Config.
Units x.x secs
Minimum Value 0.0
Maximum Value 600.0
Default Value 20.0
Maximum Freq
Accel Time
-------------------------------------- Accel Rate=
Parameter 35
(Maximum Freq)
Speed
Accel
Time 2
0
0
Time
Decel
Time 2
Acceleration
Deceleration
DecelTime2
When active, sets the rate of deceleration for all speed decreases except for jog.
Parameter Number 70
Related Parameters 37
Access Rule GET/SET
Data Type UINT
Group Advanced Config.
Units x.x secs
Minimum Value 0.0
Maximum Value 600.0
Default Value 20.0
Maximum Freq
Decel Time
-------------------------------------- D e c e l R a t e=
Parameter 35
(Maximum Freq)
Speed
Accel
Time 2
0
0
Time
Decel
Time 2
Acceleration
Deceleration