Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 121
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
Advanced Configuration
OLWarningLevel
This parameter determines the Overload
Warning Level in % Thermal Capacity Used
(%TCU).
Parameter Number 69
Access Rule GET
Data Type USINT
Group Advanced Config.
Units %TCU
Minimum Value 0
Maximum Value 100
Default Value 85
JamInhibitTime
This parameter determines the time
during motor starting that Jam detection
is inhibited.
Parameter Number 70
Access Rule GET
Data Type USINT
Group Advanced Config.
Units secs.
Minimum Value 0
Maximum Value 250
Default Value 10
JamTripDelay
This parameter determines how much
time above the Jam Level before the unit
will trip.
Parameter Number 71
Access Rule GET
Data Type USINT
Group Advanced Config.
Units x.x secs
Minimum Value 1
Maximum Value 25.0
Default Value 5.0
JamTripLevel
This parameter determines the Jam Trip
Level as a percentage of Full Load Amps.
Parameter Number 72
Access Rule GET
Data Type UINT
Group Advanced Config.
Units %FLA
Minimum Value 50
Maximum Value 600
Default Value 250