Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 133
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
Motor and Control Group
SnapShotBusVolts
This parameter provides a snapshot of DC
bus voltage level at time of last trip.
Parameter Number 26
Access Rule GET
Data Type UINT
Group Trip Status
Units V DC
Minimum Value 0
Maximum Value 1200
Default Value 0
SnapShotDrvTemp
This parameter provides a snapshot of
operating temperature at time of last trip.
Parameter Number 27
Access Rule GET
Data Type UINT
Group Trip Status
Units °C
Minimum Value 0
Maximum Value 9999
Default Value 0
MotorNPVolts
Set to the motor nameplate rated voltage.
Parameter Number 28
Access Rule GET/SET
Data Type UINT
Group Motor and Control
Units V AC
Minimum Value 35
Maximum Value 460
Default Value 460
MotorNPHertz
Set to the motor nameplate rated
frequency.
Parameter Number 29
Access Rule GET/SET
Data Type UINT
Group Motor and Control
Units Hz
Minimum Value 10
Maximum Value 400
Default Value 60
O
Stop drive before changing this
parameter.
Stop drive before changing this
parameter.
O