Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 145
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
Miscellaneous Configuration Group
NetworkOverride
This parameter allows for the local logic
to override a Network fault.
0 = Disable
1 = Enable
Parameter Number 64
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
CommsOverride
This parameter allows for local logic to
override an I/O connection timeout.
0 = Disable
1 = Enable
Parameter Number 65
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
KeypadMode
This parameter selects if the keypad
operation is maintained or momentary.
0 = Momentary
1 = Maintained
Parameter Number 66
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
KeypadDisable
This parameter disables all keypad
function except for the “OFF” and “RESET”
buttons.
0 = KeypadEnabled
1 = KeypadDisabled
Parameter Number 67
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ArmorStart 294E and is the answer not in the manual?

Allen-Bradley ArmorStart 294E Specifications

General IconGeneral
BrandAllen-Bradley
ModelArmorStart 294E
CategoryController
LanguageEnglish

Related product manuals