232 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Appendix C Using DeviceLogix™
11. From the toolbar, Click on the “Discrete Input” button and select Pt01
from the pull-down menu. This is the remote stop button based on the
example I/O table.
12. Place the input to the left of the RSL function.
13. Connect the input to the reset input of the RSL latch.
14. From the toolbar, Click on the “Discrete Output button and select
RunForward” from the pull-down menu. RunForward is the relay
controlling the coil of the contactor. Click OK.
15. Move the cursor into the grid and place the Output to the right of the RSL
function block.
16. Connect the output of theRSL” function block to Run Fwd.
17. Click on theVer i f y button located in the toolbar or select “Logic Verify”
from the “Tools” pull-down menu.
18. Click on the “Edit” button to toggle out of edit mode if online with a
device.