270 Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Appendix B Module Tag Definitions
5069-OBV8S and
5069-OBV8SK Module Tags
This section describes the tags that are associated with the 5069-OBV8S or
5069-OBV8SK module.
Input Tags
Table 91 describes the 5069-OBV8S and 5069-OBV8SK module input tags.
5069-OBV8S
SIL2 CPU
5069-L3100ERMS2
Compact GuardLogix
5069-OBV8S
5069-IB8S5069-IB8S
OUTPUT OUTPUT
SA Power MOD Power
Safety Modules
Table 91 - 5069-OBV8S and 5069-OBV8SK Module Input Tags
Name Data Type Definition Valid Values
RunMode BOOL Module’s operating state • 0 = Idle
• 1 = Run
ConnectionFaulted BOOL Indicates if a connection is running.
The module sets this tag to 0 when connected. If the
module is not connected, the controller overwrites the tag
to 1.
• 0 = Connection is working
• 1 = Connection is not working
DiagnosticActive BOOL Indicates if any diagnostics are active or if the prognostics
threshold is reached.
• 0 = No diagnostics active
• 1 = One or more diagnostics are active or the
prognostics threshold is reached
DiagnosticSequenceCount SINT Increments for each time a distinct diagnostic condition is
detected, and when a distinct diagnostic condition
transitions from detected to not detected.
Set to zero by product reset or power cycle. Wraps from
255 (-1) to 1 skipping zero.
• 1…255
Ptxx.Readback BOOL Indicates that a 24V DC power source is connected to the
output circuit
• 0 = 24V DC power is not present
• 1 = 24V DC power is present
Ptxx.Fault BOOL Indicates one of the following:
• The channel data is inaccurate and cannot be trusted
for use in the application.
For more information, see
Module Data
Quality Reporting on page 71.
• The channel is set to Not Used.
• 0 = Good data
• 1 = Bad data (faulted) or set to Not Used
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes
the tag to change to 1 is removed, you must
complete the steps described in
Safety Output
Fault Recovery on page 148 to reset this tag
to 0.
(1)
If the tag is 1 because the channel is set to Not
Used, no action is required.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Compact 5000 Series and is the answer not in the manual?

Allen-Bradley Compact 5000 Series Specifications

General IconGeneral
BrandAllen-Bradley
ModelCompact 5000 Series
CategoryI/O Systems
LanguageEnglish

Related product manuals