Rockwell Automation Publication 1756-RM003N-EN-P - October 2011 165
Input/Output Instructions (MSG, GSV, SSV, IOT) Chapter 4
MSG Error Codes
The error codes depend on the type of MSG instruction.
Error Codes
The RSLogix 5000 programming software does not always display the full
description.
Error Code (Hex) Description Display In Software
0001 Connection failure (see extended error codes) Same as description
0002 Insufficient resource
0003 Invalid value
0004 IOI syntax error (see extended error codes)
0005 Destination unknown, class unsupported, instance undefined or
structure element undefined (see extended error codes)
0006 Insufficient packet space
0007 Connection lost
0008 Service unsupported
0009 Error in data segment or invalid attribute value
000A Attribute list error
000B State already exists
000C Object model conflict
000D Object already exists
000E Attribute cannot be set
000F Permission denied
0010 Device state conflict
0011 Reply will not fit
0012 Fragment primitive
0013 Insufficient command data
0014 Attribute not supported
0015 Too much data
001A Bridge request too large
001B Bridge response too large
001C Attribute list shortage

Table of Contents

Other manuals for Allen-Bradley Logix5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Logix5000 and is the answer not in the manual?

Allen-Bradley Logix5000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelLogix5000
CategoryController
LanguageEnglish

Related product manuals