EasyManua.ls Logo

Allen-Bradley Logix5000

Allen-Bradley Logix5000
708 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
182 Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
Chapter 4 Input/Output Instructions (MSG, GSV, SSV, IOT)
Specify PLC-3 Messages
The PLC-3 message types are designed for PLC-3 processors.
The following diagrams show how the typed and word-range commands differ.
The example uses read commands from a PLC-3 processor to a Logix5000
controller.
Select this command If you want to
PLC3 Typed Read Read integer or REAL type data.
For integers, this command reads 16-bit integers from the PLC-3 processor and stores them in
SINT, INT, or DINT data arrays in the Logix5000 controller and maintains data integrity.
This command also reads floating-point data from the PLC-3 and stores it in a REAL data type tag
in the Logix5000 controller.
PLC3 Typed Write Write integer or REAL type data.
This command writes SINT or INT data, to the PLC-3 integer file and maintains data integrity. You
can write DINT data as long as it fits within an INT data type (
32,768
data
32,767).
This command also writes REAL type data from the Logix5000 controller to a PLC-3 floating-point
file.
PLC3 Word Range Read Read a contiguous range of 16-bit words in PLC-3 memory regardless of data type.
This command starts at the address specified as the Source Element and reads sequentially the
number of 16-bit words requested.
The data from the Source Element is stored, starting at the address specified as the Destination
Tag.
PLC3 Word Range Write Write a contiguous range of 16-bit words from Logix5000 memory regardless of data type to PLC-
3 memory.
This command starts at the address specified as the Source Tag and reads sequentially the
number of 16-bit words requested.
The data from the Source Tag is stored, starting at the address specified as the Destination
Element in the PLC-3 processor.
16-bit words in PLC-3
processor
32-bit words in Logix5000
controller
The typed commands maintain data structure and value.
1
2
3
4
Typed Read Command
1
2
3
4
16-bit words in PLC-3
processor
32-bit words in Logix5000
controller
The word-range commands fill the destination tag contiguously.
Data structure and value change depending on the destination
data type.
1
2
3
4
Word-range Read Command
1
3
2
4

Table of Contents

Other manuals for Allen-Bradley Logix5000

Related product manuals