Rockwell Automation Publication 1756-RM003N-EN-P - October 2011 51
FactoryTalk Alarms and Events Logix-based Instructions (ALMD, ALMA) Chapter 1
ALMD Alarm Acknowledge Required and Latched
Condition Function Block Action Structured Text Action
Prescan All operator requests, timestamps, and delivery flags are
cleared.
InAlarm is cleared and Acked is set.
All operator requests, timestamps, and delivery flags are
cleared.
InAlarm is cleared and Acked is set.
Instruction first scan No action taken. No action taken.
Instruction first run No action taken. No action taken.
EnableIn is cleared The instruction does not execute.
EnableOut is cleared.
The instruction executes.
EnableOut is always set.
EnableIn is set The instruction executes.
EnableOut is set.
The instruction executes.
EnableOut is always set.
Postscan No action taken. No action taken.