AC Input Power Connection
TM-F1OP-C1XN-01 2-7
AC Fail LED
The AC Fail (ACF) LED turns on when the input voltage is outside of the
range specified for the power supply. The LED turns off when the input
voltage is within the range.
AC Input Cord
The AC input cord we recommend is specified in Table 2-3. Add a non-
locking plug suitable for use in the country in which you are operating. If
you require a special cord, contact the manufacturer.
Table 2-2
Operational AC Input Voltage Ranges and Frequency
AC Voltage Range Frequency
85-130 Vac 1
φ (20 A maximum at 120 Vac)
a
a.6 V model: 95-130 Vac
47-63 Hz
190-264 Vac 1
φ (12 A maximum at 230 Vac) 47-63 Hz
WARNING:
The AC input cord is the disconnect device for the power supply. The plug must
be readily identifiable by and accessible to the operator. The input cord must be
no longer than 9.84 feet (3 m).
Table 2-3
AC Wire Specification
Wire Size Ratings Cable Outside Diameter
3 x 12 AWG
stranded copper
60 °C minimum, 300 V 0.545-0.708 in. (13.63-17.7 mm)
3 x 16 AWG
stranded copper
a
a.Alternate choice for 190-264 Vac input only.
60 °C minimum, 300 V 0.545-0.708 in. (13.63-17.7 mm)